Techton® 1200 Pipe Insulation

Techton® 1200 is a rigid mandrel wound pipe product made of strong, preformed stone wool insulation.

Applications:
This product is designed for moisture intense applications, such as steam and process pipe systems operating at temperatures up to 1200°F (650°C), where energy conservation, personnel protection and fire control are concerns.

Properties

  • Fire resistant; non-combustible, with melting point of approx. 2150°F (1177°C).
  • Water and moisture resistant; impregnated with high-water repellent characteristics
  • Non-corrosive
  • Lasting thermal performance not compromised by water
  • Controls sound transmission due to:
    • Non-directional fiber composition and density
    • Tight, seamless joints
  • Easy to handle and cut with a knife for easy installation
  • Individual computer needs analysis available (in accordance with the NAIMA 3E Plus software program)

Tecnical Data

Compliance and Performance:
ASTM C 547Standard Specification for Mineral Fiber Preformed Pipe Insulation Type I, II, IV, Complies Grade A
CAN/ULC S114Test For Non-Combustibility Non-Combustible
ASTM E 136Behavior Of Materials at 750 C (1382 F)Non-Combustible
CAN/ULC S102 Surface Burning CharacteristicsFlame Spread = Passed
Smoke Developed = Passed
ASTM E 84(UL 723)Surface Burning Characteristics  Flame Spread = Passed
Smoke Developed = Passed
ASTM C 411Hot Surface Performance In Compliance with ASTM C547 @ 1200°F (650°C)
ASTM C 447 Maximum Surface Performance In Compliance with ASTM C547 @ 1200°F (650°C)
ASTM C 795 **** Stainless Steel Stress Corrosion Specification as per Test Methods C871 and C692: U.S. Nuclear Regulatory Commission, Reg. Guide #1.36: U.S. Military SpecificationsConforms
ASTM C 356Linear Shrinkage≤ 1.30% @ 1200°F (650°C)
ASTM C 1104 Moisture Sorption < 0.1%
ASTM C 585 Inner & Outer Diameters for Nominal Pipe Sizes Complies
ASTM C 800WickingZero

Thermal Conductivity (k):


                                                                                Horizontal Pipes

Ambient Temperature:75°FNT: Nominal Thickness
Wind speed:1 mph HL: Heat Loss (Btu/ft/hr)
Base Metal:Steel ST:Surface Temperature (°F)
Emittance of outer jacketing: 0.1 NPS:Nominal Pipe Size